Skip to main content

EN54 Voice Alarm System - C500/3+1

Item Number: 2310221020

EN54 Voice Alarm system

  • EN54 certified voice alarm system
  • Complete system in a box
  • Extend with networking capabilities
  • Wide range of features
  • Easy to install and operate
  • Ideal for schools and buildings where safety is of critical importance
EN 54 Certified

The C500 EN54 voice alarm system is ideal for schools and buildings where safety is of critical importance. The system supports system in a box concepts that gives you the benefits of a compact EN54 installation. In addition you can extend your system by networking of modules to grow bigger systems.

Capacity - single module
Number of zones 6
Total output power 600 watt (420W RMS continous)
Power amplifiers 6 x 100W (2 amplifiers can be bridged to 1 x 200W)
Standby amplifier 2 x 100W (or bridged to 1 x 200W)
Loudspeaker line
Monitoring 20 kHz AC monitoring with EOL module,
Short/open/impedance monitoring
Loopdrive monitoring DC monitoring with short circuit isolators (EN54-17)
Short/open/earth leakage
Loudspeaker type 100 volt
Voice messages
Storage 16 audio files x 1 minute
Message player 6 simultanious local playbacks
Control and indications
General controls Lamp test button, silence button
General indicators Power, Evac, Fault (LED)
Fault indications Power, System, Network and Zone faults
Evac manual control Evac message, Alert message
Silence, Reset
Integrated fireman microphone
Zone controls 6 x configurable zone select buttons
Zone indicators Evac, Fault, Busy (LED)
Fireman microphone Priority, Electrical monitoring of mic/panel
Power supply equipment
AC supply 110 - 230 VAC
AC current consumption Max 5,3 A @ 155 VAC / 2,65 A @ 230 VAC
Inrush current 40 A @ 115 VAC / 20A @ 230 VAC
Power supply protection Overload current limiting
Over voltage shutdown
Over temprature shutdown
Battery
Type Sealed, rechargeable, lead-acid
Capacity , charging time 10-55 AH, <20h @ 80% capacity
Rated voltage 24 VDC (2 x 12 VDC)
Battery dimension 2 x batteries of max 230x138x207 mm
Battery weight Max total 32,6 kg
Inputs and outputs
Inputs
2 x BGM 2 x balanced mono, 22 kΩ impediance
6 x EVACin Monitored logic inputs, 4,7 - 10 kΩ EOL resistor
1 x SILENCE in Monitored logic inputs, 4,7 - 10 kΩ EOL resistor
1 x RESET in Monitored logic inputs, 4,7 - 10 kΩ EOL resistor
8 x GPI Unmonitored logic inputs (pull down, configurable)
Outputs
EVAC out Potential free relay output
FAULT out Potential free relay output
8 x GPO Open collector output
6 x loudspeaker out 6 x 100 volt transformer output
Amplifiers
Type Class D
Protection Overload shutdown
Over temprature shutdown
Backup amplifiers 2 x backup channels
Efficiency 80% @ rated power
Output voltage 100 volt RMS
Rated power 100 W per channel / 200 W bridged
Output bandwidth 50 Hz - 20 kHz
SNR > 80 dB
THD + N 0,1% @ rated power
Audio
Frequency response 50 Hz - 20 kHz (BGM)
100 Hz - 12 kHz (message player, network audio)
Input-output latency < 10 ms (standalone system)
Digital audio format 24 kHz sampling, ADPCM coding
DSP features HP/LP filter, Multi-point parametric EQ, Delay
Mechanical
Dimensions (HxWxD) 80 x 52 x 28 cm
Packaging (HxWxD) 90 x 60 x 36 cm
Weight without batteries 29 kg
Housing material Steel / ABS
IP rating IP30
Mounting Wall mount
Network system
Max number of modules 255
Max number of zones 255
Max capacity 102 kW
Simultaneous calls 2
Simultaneous message playback 16
Local network
Arcitecture Master : 16 slaves
Connections 3 x L-Net port, daisy chain bus
Cabling X-over FTP CAT6E
Max bus length 250 m (default)
500m (network extender)
Global network
Architecture Peer to peer
Connections 2 x G-Net port
Cabling X-over FTP CAT6E
Max distance 250 m (default)
750m (network extender)
2500 m (fiber extender)

No documents available for this product.